Power Distribution Cubicles
Product Specifications & Details
Product Description
The Point Power Supply Cubicle is a high-reliability three-phase power supply system engineered to deliver a steady 110V DC output for operating multiple Metro point machines simultaneously across rail networks. Built around a robust three-phase transformer, full-wave rectifier, and smoothing circuit, the system matches the stringent requirements of RDSO specification IRS:S:91/2014 to ensure maximum operational safety and performance.
Designed for continuous heavy-duty service in transit control hubs and maintenance depots, the system incorporates two identical Transformer Rectifiers connected through O-Ring diodes to provide full output redundancy. Its compact standalone cubicle layout optimizes floor space while integrating comprehensive protection, distribution breakers, digital metering, and optional insulation monitoring devices for effortless maintenance and system diagnostics.
Key Features
- Redundant Power Supplies: Dual identical Transformer Rectifier units tied via O-Ring diodes to ensure continuous, uninterrupted power switchover.
- Compact Footprint: Standalone floor-standing cubicle designed to occupy minimal floor space in station equipment rooms.
- RDSO Compliance: Manufactured in strict accordance with the functional and performance characteristics of RDSO specification IRS:S:91/2014.
- Ease of Maintenance: Engineered for easy front and rear access with standard 22.5 mm Ø LED indicators for input and rectifier output status.
- Flexible Customization: Integrated distribution circuits, voltage monitoring relays, insulation monitoring devices (IMD), and voltmeters/ammeters tailored to client schematics.
- High-Current Capacity: Scalable output current ratings from 30A up to 200A to support heavy simultaneous point machine operations.
IRS:S:91/2014
Application
Metro rail depot installations, passenger yards, and junction stations requiring reliable 110V DC power delivery for simultaneous point machine operations.
Technical Specifications Data Sheet
| Parameter | Technical Requirement / Standard Specification |
|---|---|
| Input Voltage | 415V AC, Three Phase, 50Hz |
| Off Load Tappings (Input) | As per customer requirement (Standard: 380V – 400V – 415V) |
| Output Voltage | 110V DC |
| Off Load Tappings (Output) | As per customer requirement (Standard: 110V – 120V – 130V) |
| Current Rating | 30A to 200A (or custom configured) |
| Voltage Tolerance | ±2.5% at Rated Load |
| Voltage Regulation (Transformer) | < 5% |
| Voltage Regulation (Unit) | < 10% (Before O-Ring Diode) |
| No Load Current | < 10% of Rated Full Load Current |
| Overall Efficiency | > 70% (At Nominal Input and Max Output) |
| Insulation Class & Voltage | Class H | 2 kV AC for 1 minute (Input/Output, Input/Earth, Output/Earth) |
| Insulation Resistance | Transformer: > 1000 MΩ | Complete Unit: > 10 MΩ |
| Operating Temperature & RH | -10°C to +55°C | RH < 90% |
| Status Indications | 22.5 mm Ø LED Lamps for Input and Both Rectifier Outputs |
Related Products
More equipment from Power Equipment
Choke Coil Type B
Track Feed Battery Charger